Product Safety Report Reference 2412-0006

FOLO-UP Product Safety Report: 2412-0006 CIAT VECTIOS Roof Top Air Handling Unit

Roof top air handling unit with heaters for commercial, industrial or office buildings.

Recorded risk Low Source updated 30 April 2025

Why this product was flagged

Recorded hazard

It is possible for a relay to fail closed, permanently energizing the heater and creating a low risk of a limited thermal event.

What the notice records

Corrective action

The manufacturer has initiated a modification programme. The manufacturer has contacted distributors and end users requiring, at the next intervention or maintenance visit, the addition of hardware (circuit breaker) to the relay contactor to shut down power as soon as relay failed closed is detected. Intervention and material kits are to be provided free of charge.

Identify the product

Product details

Product
CIAT VECTIOS Roof Top Air Handling Unit
Brand
CIAT
Models
Not provided
Product type
Roof Top Air Handling Unit
Seller or shop
Unknown
Country of origin
Spain
Measure
Modification programme
Notified by
Health and Safety Executive

Found this product online?

Flag the listing while the evidence is visible.

A Whistle report is a listing signal submitted for evidence capture and controlled human review. It is not treated as a confirmed listing match until checked.

Get FOLO-UP Whistle